Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2005 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 06/30/2005 | EXCAVATION/LAYOUT REBAR & ZON | Cancelled | ||
| 06/28/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REBAR TO BE A MINIMUM OF 3" FROM DIRT ALL AREAS 2) RACK VERTICAL REBAR IN PLACE 3) SOME GRADE STAKES ARE LESS THAN 12" MINIMUM CONCRETE DEPTH REQUIRED |
|
| 06/23/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GRADE PINS NOT SET AT MINIMUM 12" THICK CONCRETE 2) MAINTAIN MINIMUM 3" CLEARANCE REBAR TO DIRT 3) FTGS NOT 18" WIDE 4) PLAN SHOWS STAIRS ON EAST SIDE OF DECK, LAYOUT IS FOR STAIRS ON WEST SIDE OF DECK 5) CANNOT LOCATE ENGINEER DETAIL 6) STOPPED INSPECTION 7) ELECTRIC (REAR) NOT ON PLAN ? 8) REFEE DUE |
|
| 06/21/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) (FRONT PORCH) REAR INCOMPLETE 2) PLAN CALLS FOR 18" WIDE FTGS AND 12" DEEP 3) MUCK OUT FTG AFTER MAINTANCE 18" X 12" FTGS 4) MAINTAIN MINIMUM 3" CLEARANCE REBAR TO DIRT |
|
| 06/17/2005 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FOOTINGS NOT TO PLAN/CODE 2) MAINTAIN MINIMUM CLEARANCE REBAR 3" TO DIRT 3) REMOVE P.V.C. H20 LINE FROM FTG 4) INCOMPLETE 5) STOPPED INSPECTION |