Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM00226
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2005 | ELECTRIC - ABOVE CEILING | Approved | ||
09/26/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
09/25/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WIRES SUPPORTING ELECTRIC TO BE AS PER 300.11. 2. REMOVE OLD M/C CABLES BACK TO BOX. 3. ATTACH FIXTURES TO GRID 410.16. 4. SUPPORT VDV CABLING AS PER 725.2 & 6, 760.2 & 6, 800.2 & 6 5. STRIP LIGHTING TO HAVE SUPPORT WIRES. |