Permit: T05CM00226

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM00226

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2005 ELECTRIC - ABOVE CEILING Approved
09/26/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
09/25/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :* 1) WIRES SUPPORTING ELECTRIC TO BE AS PER 300.11. 2. REMOVE OLD M/C CABLES BACK TO BOX. 3. ATTACH FIXTURES TO GRID 410.16. 4. SUPPORT VDV CABLING AS PER 725.2 & 6, 760.2 & 6, 800.2 & 6 5. STRIP LIGHTING TO HAVE SUPPORT WIRES.