Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM00206
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
04/22/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*UNIT C PROVIDE 2 OPENINGS IN DOOR FOR COMBUSTION AIR M?? 100 SQ IN EACH OPENING |
|
04/14/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PETITION OF APPEAL UNIT "C" EXTEND DRYER VENT OUT OF THE WALL IN LAUNDRY AREA 2) PROVIDE SCREWS IN FURNACE VENT CONNECTOR 3) WATER HEATER VENT CONNECTOR FITTING UPSIDE DOWN 4) UNIT "B" PROVIDE A SINGLE WALL VENT CONNECTOR ON WATER HEATER, NOT DBL WALL WITH THE INSIDE REMOVED 5) UNIT "A" PROVIDE A NIPPLE FOR GAS CONNECTION TO FURNACE 6) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR 7) PROVIDE 26 GA. GALVANIZED VENT CONNECTOR ON WATER HEATER, NOT THE INSIDE PIECE FROM UNIT B 8) UNIT "D" DBL WALL VENT FOR FURNACE IS MISSING THE INSIDE PIECE |