Permit: T05CM00205

Parcel: 140376990


Addresses:

5938 E CURLEW LN

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/08/2005 FRAMING Approved IVRS - Inspection :*
06/08/2005 FRAMING Partial Approval IVRS - Inspection :*
1) OK TO INSULATE AND DRYWALL
2) REPAIR IS PER ENGINEERING DOCUMENT DATED 6/5/05. REPAIR DOCUMENT MUST BE CITY APPROVED
3) OK TO CONTINUE
06/07/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TRUSS IS A STUBED TRUSS AND REAPIR DOCUMENT SHOWS A CONVENTIONAL TRUSS. CORRECT DRAWING
2) WEST REPAIR IS MADE UP OF THREE PIECES OF O.S.B. DRAWING SHOWS ONLY ONE. ENDS AND EDGES OF REPAIR PIECES ARE NOT BLOCKED OR NAILED. HAVE ENGINEER SPECIFY EXACTLY HOW TRUSS IS TO BE REPAIRED
3) HAVE ENGINEERING APPROVED BY CITY OF TUCSON
05/10/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM 7 FROM 5/5/5 NOT COMPLIED WITH
2) OK TO INSULATE AND PARTIAL DRYWALL
3) DO NOT COVER-2ND FLOOR TRIPPLE TRUSS
4) ALL ELECTRIC OK BUT TRIPPLE GIRDER TRUSS
05/05/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 7/SD2 AT SHEAR WALL G-3 NOT COMPLIED WITH BLOCSK REQUIRED EACH SIDE OF RANGE DUCT CUTS AND SEE NAIL SCHEDULE
2) SEAL FLOOR PENETRATIONS AT TUB
3) STAIR LIGHT SWITCH IS BEHIND HANDRAIL
4) NAIL 2ND FLOOR SHEAR WALL BOTTOM PLATES AT 12" ON CENTER
5) ELECTRIC OUTLET REQUIRED WITHIN 6 FEET OF STAIR TOP AT PONY WALL
6) NAIL 2ND FLOOR SILL PLATES AT 16' ON CENTER
7) TRIPPLE GIRDER TRUSS HAS 7 EACH HOLES DRILLED. PROVIDE CITY OF TUCSON APPROVED TRUSS ENGINEERING APPROVED REPAIR
8) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE
05/04/2005 FRAMING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
1) 2889B HOUSE 2082 PLAN AND TRUSS DRAWINGS
2) NO PLANS ON SITE, NO INSPECTION