Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM00186

Parcel: 11720029A


Addresses:

260 S CHURCH AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM00186

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
01/15/2005 MECHANICAL - INTERMEDIATE Partial Approval 1) SUSPENDED DUCT AND DIFFUSERS OK
2) FINISH INSTALLING SOUND CONTINUATORS AND FINAL CONNECTIONS TO FIRE/SMOKE DAMPERS
3) BE SURE ALL VOIDS AROUND DAMPERS AR FILLED
4) PROVIDE ACCESS DOORS WHERE NECESSARY
5) FILL ANY SMALL GAPS ON ANGLE IRONS AND DUCTS WITH FIRE CAULK
6) COLLECTED $108.00 CHECK