Permit: T05CM00186

Parcel: 11720029A


Addresses:

260 S CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM00186

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* LAS 4 FIXTURES CHECKED TODAY- REST OF JOB CHECKED BY DAN SANTA CRUZ
01/24/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* NOTES: 1) OK WORK DONE BY THIS CONTR. PER PERMIT & APPROVED PLANS. HOWEVER UNSAFE CONDITIONS EXSIST. SEE PREVIOUS NOTES. INSP 1/20/05
01/20/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* ALSO MUST VERIFY STEMS FOR HY BAY FIXTURES WRENCH TITE PER PREVIOUS INSPECTIONS, FIXTURES IN MIDDLE OR CENTER SECTION NOT WORKING SEE NOTES PREVIOUS INSPECTIONS. ALSO UNSAFE CONDITIONS EXSIST OF POWER & COMM. CONDUITS NOT SUPPORTED IN CEILING NOT IN SCOPE OF WORK PER THIS CONTR. PER APPROVED PLANS. POSSIBLY DAMAGED BY FIRE CLEAN UP . ?? LIGHTNG OK GENERATOR TEST OK POSSIBLE FIRE DAMAGE TO CONDUCTORS IN EXSISTING CONDUITS.
01/19/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*1) FINAL SUBJECT TO FUNCTIONAL EM. LIGHTING SYSTEM CHECK OU. 2) REPAIR NOW OPERATIONAL LIGHT FIXTURE. CENTER AREA. 3) VERIFY FIXTURE STEMS WRENCH TITE. 4) ALL PANEL COVERS INPLACE & UPDATED PANEL SCHEDULES.
01/17/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*