Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM00186
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTES: 1) COMPLETE LAMPING FIXTURES. 2) COMPLETE WIRE ( BRANCH CIRCUIT) MAKE-UP. 3) CLOSE J-BOXES & PLUG UNUSED KD'S IN BOXES. 4) COMPLETE TIGHTENING FOR FIXTURE STEMS. 5) NEED ARCH. APPROVAL & CUT SHEET FOR MOUNTING DETAIL OF LIGHT FIXTURES IN HIGH BAY AREA, CONT. INSTALLATION NOT PER PLAN. 6) LOW VOLTAGE CONTROL SYSTEM NOT COMPLETE | |
01/17/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BONDING DEVICES FOR FITTING OVER 250 VOLT TO GROUND AT CONCENTRICS 2) PENDENT LIGHTS TO BE MAD UP "WRENCH TITE" 3) FINISH SUPPORTING VDV CABLEING AND REMOVAL OF OLD 4) RECEIVED CHECK #2883 FOR 2 AFTER HOURS INSPECTIONS #216.00 |
|
01/14/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1) M/C CABLE TO BE INDEPENDENTLY SUPPORTED 2) FIXTURE WHIPS NOT LISTED FOR CIRCUIT CONDUCTORS 3) BONDING DEVICE FOR FITTING OVER 250 VOLT TO GROUND AT CONCENTRICS 4) VDV CABLEING TO BE AS PER 725.2, 725.6, 800.6, 760.2 AND 760.6 5) PENDANT LIGHTS TO BE MADE UP "WRENCH TITE" 6) PROTECT VDV CABLEING WHERE ENTERING CONDUITS AND TIGHTEN LOOSE FITTINGS AND SUPPORTS 7) RECEIVED MONEY ORDER #53585922379 |