Permit: T05CM00176

Parcel: 117091690


Addresses:

1017 S HERBERT AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/21/2006 FRAMING Approved IVRS - Inspection :*
12/18/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FIRE STOP AT TOP PLATE COMPLY WITH DETAIL
2) S-3 FOR GROUTED ANCHOR TO BEAM CROSS BRACE TRUSSES AT MID-SPAN
3) EXTEND 3/4" 18" MINIMUM VENT AT W/H CONNECTION
4) MOVE PEX WATER LINES 12" MINIMUM FROM ELECTRIC CAN LIGHTS
5) COMPLETE PTR LINE INSTALLATION
6) PVC NOT APPROVED USE CPVC