Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 06/15/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 06/08/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) STUCCO LATH NOT NAILED AT BOTTOM PLATES AT 6" ON CENTER 2) GARAGE P-3 SHEAR WALL REQUIRES HILTI PINS AT 3" ON CENTER 3) 2A HOLDOWN WRONG LOCATION MUST BE 13'-11" FROM OUTSIDE WALL ON DBL STUDS 4) CHANEL AT GARAGE NOT NAILED PER 10/SD4 5) WEST SHEARWALL REQUIRES ANCHOR BOLTS AT 16" ON CENTER 6) PLUMBING LEAK AT TUB 7) DUCT WORK RESTRICTED BY PLUMBING-GREAT ROOM 8) STOPPED INSPECTION-TO MANY ITEMS |