Permit: T05CM00115

Parcel: 11615088L

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM00115

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/08/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 1/2" EMT CONDUIT NOT SUPPORTED, LAYING ON LIGHT FIXTURE EAST END OF CORRIDOR 3RD FLOOR
08/04/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK ELECTRICAL CONTR, INSTALLATION FOR NEW WORK, HOWEVER THERE ARE EXISTING BOXES, CABLING AND SOME NEW CABLING NOT SUPPORTED OR SUPPORTED ON CONDUIT, MUST HAVE OWN SUPPORTS CANNOT LAY ON GRID FOR COILING PER 2002 NOC
07/28/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK 3RD FLOOR 3300 WING