Permit: T05CM00101

Parcel: 107132520


Addresses:

462 E KELSO ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05CM00101

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/24/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
04/20/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNCOVER ALL UNDERGROUND PIPING
2) EXPOSE ABOVE GROUND GAS PIPING RUSTED-HAVE ENGINEERING CERTIFIED OR REPLACE
3) SECURE PIPING TO WALL
4) CANNOT HAVE GAS PIPING IN RETURN AIR PLENIUM
5) SUBMIT GAS DRAWING SHOWING ALL GAS APPLIANCE DEMANDS, LENGTH OF RUN SIZE OF PIPE, ETC...
6) STOPPED GAS INSPECTION