Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/10/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) FRAME PARTIALLED UNTIL MECH INTERMEDIATE |
|
| 02/09/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTERIOR SHEATHING MUST BE NAILED AT 6" ON CENTER ENDS AND EDGES AND 12" IN FIELD 2) MAKE UP ALL GROUND WIRES IN ELECTRIC BOXES AND SECURE WITH MECHANICAL FASTENERS 3) GROUND ALL METAL ELECTRIC BOXES 4) HANRD WIRED SMOKE DETECTOR REQUIRED IN BEDROOM |