Permit: T05CM00081

Parcel: 12218274A


Addresses:

1160 N WINSTEL BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/17/2005 ELECTRIC - FINAL Approved
03/11/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) CONDUCTOR NOT INSTALLED AS PER PLANS. NO ISOLATED GROUND 2) IDENTIFY GROUNDING CONDUCTOR AND TIGHTEN LOOSE TERMINATION. 3) FILL UNUSED OPENING IN PANEL. 4) PANEL DIRECTORY NOT CORRECTLY LABELED. 5) PLEASE REVISE PLANS FOR EQUIPMENT AND CIRCUIT & ?? CHANGES, NEED CONTROL PANEL ON PLANS. 6) RECEPTACLE COVER TO BE WEATHERPROOF WETHER OR NOT PLUGGED IN 408.6. 7) THIGHTEN LOOSE SEAL TITE FITTINGS. 8) DISCONNECTS TO BE IDENTIFIED TO WHICH UNIT IT CONTROLS. 9) TIGHTEN LOOSE TERMA?? AT MAIN BREAKER.