| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* FINAL IS ALSO SUBJECT TO PARKS & ELECT KEN KALTHOFF ON MINOR CHANGES | |
| 11/07/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RECALL AND LEAVE MESSAGE AND PHONE # SO I CAN CALL YOU AND SET UP TIME |
|
| 11/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*MAIN BREAKER IN NEW PANEL REQUIRES A RETAINER CLIP SEAL HOLES IN EQUIPMENT IN CABINET SCOTCH VOTE( WEATHER PROOF SPLICES IN UNDERGROUND BOXES,ID CONDUCTORS AT 1ST J-BOX NEAR CABINET |