Permit: T05CM00063

Parcel: 140375960


Addresses:

6952 S GOSHAWK DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/22/2005 BUILDING - FINAL Approved IVRS - Inspection :*
08/19/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WIRES IN PANEL BY OVERTORQUE. REPAIR ALL WIRES IN PANEL
2) DOUBLE LUGGING OF NEUTRALS NOT ALLOWED
3) FILL OPEN KNOCK OUTS IN PANEL
4) OUTSIDE HOSE BIBS REQUIRE ANTISIPHON VALVES
5) MICROWAVE MISSING OTULET COVER
6) POWER ROOM FAN MISSING
7) FURNACE SRU SU CABLE
8) FURNACE SPARK SHIELD NOT PROPERLY INSALLED MUST BE UNDER BURNERS
9) FURNACE "B" VENT WITHIN 1" OF COMBUSTABLES