Permit: T05CM00063

Parcel: 140375960


Addresses:

6952 S GOSHAWK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/22/2005 FRAMING Approved IVRS - Inspection :*
07/18/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PROVIDE TRUSS REPAIR DOCUMENTS
07/05/2005 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Nail protect wires within 1 1/4" of stud surface
Truss gang nails damaged
P-10 trusses (4) each have damaged gang nails
Provide city of tucson approved truss repair documents
06/30/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HIP HANGER NOT NAILED
2) STAIR WINDOWS MUST BE 6"
3) ITEM 6, 8 AND 11 FROM 6/27/05 NOT DONE
4) ITEM 12 AND 13 NOT DONE
5) STAIR PITCHED MORE THAN 1/4" PER FT
6) EXHAUST FAN NOT IN 1/2 BATH
7) BLOCK DUCTS
06/27/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) HIP JACK DOES NOT PLANE WITH CEILING AND DOES NOT ????. 2) SEAL FLOOR PENETRATIONS. 3) NAIL SW 3 AT ?? AT 3" O.C 4) WI?? REQUIRES 6" ON NARROW END. 5) F-4 TRUSS NOT BEARING ON END. 6) P-3 SHEAR REQURES PINS AT 3" O.C . 7) F-2 TRUSS NOT BEARING AT MIT PT. 8) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE. 9) STAIR LEDGER NOT SUPPORT STAIRS. NOT PER PLAN. 10) RISE OF STAIR TRENDS EXCEEDS 3/8". 11) EACH P-10 TRUSS GANG NAIL DAMAGED PROVIDE ENGINEER & COT APPROVED REPAIR. 12) TOP STAIR RUN LESS THAN 10" . 13) P-1 SHEAR WALL PLATE NOT NAILED AT 12" O.C BEHING TUB. 14) REMOVE NAILS AT PLUMBING 15) FIRE STOP 6" DUT BY TUB. 16) NAIL PROTECT PLUMBING WHITHIN 1 1/4 OF STUD SURFACE. 17) DUCT RESTRICTED BY PLUMBING.
06/24/2005 FRAMING Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
1) STAIR WINDERS MUST BE A MINIMUM OF 6" ON NARROW END
2) NO PLANS ON SITE