Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* LETTER FROM ARCH ON USE OF 1/0 FEEDERS OK |
|
| 05/17/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TAKE FEEDERS OUTSIDE TO SERVICE AREA & SUPPORT INSIDE WALLS AS PER NEC, ALSO ROMEX CIRCUITS. 2. HAVE ARCH. STAMP REVISION & INDICATE ALUMINUM SIZE ON FEEDERS. |
|
| 05/11/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. FEEDER NOT INSTALLED AT SERVICE AREA. 2. CHECK CLEARANCES FOR CABLES THRU STUDS, MUST HAVE 1 1/4" MIN. FROM STUD FACE - BOTH SIDES. 3. FEEDERS TO BE COPPER UNLESS NOTED OTHERWISE PER PLAN |
|
| 05/05/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. KITCHEN COUNTER OUTLETS ARE SPACED TO FAR APART NEC 210.52(C) 2. KITCHEN COUNTER OUTLET CAN'T SUPPLY OTHER LOADS THAN SPECIFIED IN NEC 210.52(B) 3. PROVIDE OUTLET IN EACH HALLWAY NEC 210.52(H) 4. INSTALL FEEDERS AND REMOVE BONDING SCREWS IN SUB-PANELS. *NOTE: WIRING STILL IN PROGRESS, CALL WHEN FINISHED, ALSO, PROVIDE SERVICE OUTLET FOR ROOF EQUIPMENT. |