Permit: T05CM00050

Parcel: 11507094C


Addresses:

309 W ELM ST #1101

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/26/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
LETTER FROM ARCH ON USE OF 1/0 FEEDERS OK
05/17/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TAKE FEEDERS OUTSIDE TO SERVICE AREA & SUPPORT INSIDE WALLS AS PER NEC, ALSO ROMEX CIRCUITS.
2. HAVE ARCH. STAMP REVISION & INDICATE ALUMINUM SIZE ON FEEDERS.
05/11/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. FEEDER NOT INSTALLED AT SERVICE AREA.
2. CHECK CLEARANCES FOR CABLES THRU STUDS, MUST HAVE 1 1/4" MIN. FROM STUD FACE - BOTH SIDES.
3. FEEDERS TO BE COPPER UNLESS NOTED OTHERWISE
PER PLAN
05/05/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. KITCHEN COUNTER OUTLETS ARE SPACED TO FAR APART NEC 210.52(C)
2. KITCHEN COUNTER OUTLET CAN'T SUPPLY OTHER LOADS THAN SPECIFIED IN NEC 210.52(B)
3. PROVIDE OUTLET IN EACH HALLWAY NEC 210.52(H)
4. INSTALL FEEDERS AND REMOVE BONDING SCREWS IN SUB-PANELS.
*NOTE: WIRING STILL IN PROGRESS, CALL WHEN FINISHED, ALSO, PROVIDE SERVICE OUTLET FOR ROOF EQUIPMENT.