Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 02/28/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TOP CHORD OF GABLE TRUSS OVER NOTCHED 2) INSULATE CHANNELS 3) SHEATHING AT PATIO MUST SPAN TWO BAYS 4) NAIL PROTECT ELECTRIC AND PLUMBING FROM OUTSIDE 5) CLIP NOT NAILED NORTH WALL AND STUD NOT NAILED 6) LADDER NOT SECURED 7) STOPPED INSPECTION |
|
| 02/25/2005 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) A-11-TRUSS CALLS FOR CONTINOUS BRACING AT WEB #5-11 2) USE 16D COMMON NAILS IN HUS24 HANGER 3) MISSING WIND BRACING ON WALLS 4) BLOCKING PANELS, 4/SD4 5) ROOF NAILING OK, EXCEPT BLOCKED PANELS 6) PLANS, TRUSS DRAWINGS NEED TO BE PUT IN ORDER AND STAPLED TOGETHER |