Permit: T05CM00023

Parcel: 12801005H

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/06/2005 FRAMING Approved IVRS - Inspection :*
04/04/2005 FRAMING Partial Approval IVRS - Inspection :* GET REVISION FOR FRAMING CHANGE
04/01/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*SEE DETAIL 210/S301. FRAME PENT HOUSE ACCORDINGLY
03/30/2005 FRAMING Partial Approval IVRS - Inspection :* 1) PROVIDE ALL SPECIAL INSP. REPORTS FRO WELDS AND HIGH STRENGH BOLTING. 2) REPAIR/ADD MONOKOTE AS NECESSARY ON BEAMS AND COLUMNS TO MAINTAIN 1B CONSTRUCTION
03/29/2005 FRAMING Partial Approval IVRS - Inspection :* I STILL NEED RFI FOR NORTH EXTERIOR WALL. OK TO COVER NORTH INTERIOR WALL
03/25/2005 FRAMING Partial Approval IVRS - Inspection :*
1) STAIR WRAP
03/24/2005 FRAMING Partial Approval IVRS - Inspection :* 1) CORRIDOR CEILING OK. 2) FRONT WALL NOT PER PLAN SEE DETAILS 5 & 7 ON ?? 3) RFI ENGINNER FOR APPROVAL OR FIX OF AS-BUILT NORTH WALL
03/21/2005 FRAMING Partial Approval IVRS - Inspection :* 1 HR CORRIDOR WALL.
03/09/2005 FRAMING Partial Approval IVRS - Inspection :* FIRE RATED CORRIDOR MUST BE CONSTRUCTED AS SUCH. YOU NEED PP A 3.0 FOR DETAILS ACCORDING TO PLAN-BUT THAT IS WRONG. PROVIDE CUT SHEETS FOR ANY FIRE STOP ASSEMBLY YOU MAY USE. PROVIDE ARCHITECT ACCEPTANCE FOR CORRIDOR WITH RATED CEILING OTHERWISE.