Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/19/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO DWV WATER TEST 2) RED HEAD ANCHOR BOLTS LOOSE 3) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 4) NORTH TOILET VENT MUST BE 10 FEET HORIZONTAL OR 3 FEET ABOVE AIR INTAKE 5) HEADERS MUST BEAR ON TRIMMERS 6) GFCI REQUIRED WITHIN 24" OF COUNTER END AND SINK 7) MAKE UP ALL GROUNDS |