Permit: T05CM00014

Parcel: 140383560

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/18/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/11/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) REAR PORCH POST NOT ANCHORED
2) OK TO DRY HOUSE NOT PORCH POST
04/04/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO TRUSS BRACING ON BOTTOM CHORDS OF TRUSSES WITH DEAD-WOOD BELOW A01A
3) SHEARWALL 6 REQUIRES A35 CLIPS AT 12" ON CENTER
4) STRAP CORNERS WITH NON OVERLAPPING DBL TOP PLATES
5) PORCH POST BOTTOM PLATE NOT BEARING ON FOOTING BELOW
6) X BRACE GABLE END TRUSSES AND EVERY 25 FEET THERE-AFTER
7) HINGE BRACES NOT NAILED THRU ROOF SHEATHING PER 6/DT-1