Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM00003
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/18/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/15/2005 | PLUMBING - INTERMEDIATE | Cancelled | ||
| 07/15/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/12/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) GENERAL REQUIREMENT #13 DOES NOT ADDR3ESS HOT WATER RETURN-WHERE ALL HOT WATER AND ALL RETURN PIPING TO BE INSULATED. NO PROVISION MADE FOR INSULATING HOT. NO HOT RETURN LINE INSTALLED 2) EXPANSION TANK NOT SUPPORTED 3) ALL ABOVE GRADE PIPING TO BE SUPPORTED TO TABLE 3-1 94 UPC 4) OK TO COVER UNDER SLAB 5) ABS INCOMPLETE |