Permit: T05BU02809

Parcel: 141110550

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Permit Number - T05BU02809

Inspection Description - POOL/SPA FINAL/BARRIER

Inspection Status - Approved

Date Description Inspector Results Comments
04/21/2006 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection :*
1) NO SVRS REQUIRED
03/17/2006 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/17/2006 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SPA: NEED SQUARE "D" TWO 80 AMP POLE AT SERVICE PANEL OR A LISTING FROM MANUFACTURER TO USE TYPE INSTALLED
2) SPA REQUIRES A CLASS A TWO POLE GFCI 60 AMP BREAKER FOR SPA
3) USE #6 CU. WIRE ONLY FROM SPA TO GFCI BREAKER
4) BOND METAL FENCE AT SPA TO SPA MOTOR
5) INSTALL GFCI 60 BREAKER IN SEPERATE BOX
-------------------------------------------------------------------------------------------------
1) POOL: NEED 90 DEGREES ON VACUUM BREAKER FOR DRAIN SYSGEM IS A #6
2) VERIFY GROUND WIRE AL. FROM SERVICE TO POOL PANEL