Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T05BU02809
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2006 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection :* 1) NO SVRS REQUIRED |
|
03/17/2006 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
02/17/2006 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SPA: NEED SQUARE "D" TWO 80 AMP POLE AT SERVICE PANEL OR A LISTING FROM MANUFACTURER TO USE TYPE INSTALLED 2) SPA REQUIRES A CLASS A TWO POLE GFCI 60 AMP BREAKER FOR SPA 3) USE #6 CU. WIRE ONLY FROM SPA TO GFCI BREAKER 4) BOND METAL FENCE AT SPA TO SPA MOTOR 5) INSTALL GFCI 60 BREAKER IN SEPERATE BOX ------------------------------------------------------------------------------------------------- 1) POOL: NEED 90 DEGREES ON VACUUM BREAKER FOR DRAIN SYSGEM IS A #6 2) VERIFY GROUND WIRE AL. FROM SERVICE TO POOL PANEL |