Permit: T05BU02579


Addresses:

8770 E HONEYBEAR PL

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
02/21/2006 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
11/30/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) CONDUIT TO POOL FROM SWITCH AND FILTER AREA OK
2) GROUND WIRES OK
11/25/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
11/22/2005 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXPOSE ALL CONDUIT (POOL LIGHTING RUN SO I CAN VERIFY DEPTH OF PVC). PVC TO BE MINIMUM 18" DEPTH EXCEPT COVERED BY CONCRETE
2) ALSO POOL PANEL DOESN'T HAVE THE REQUIRED WORKING CLEARANCE DUE TO POOL EQUIPMENT AND PIPING
3) POOL PANEL REQUIRED TO HAVE AN INSULATED GROUNDING CONDUCTOR PER NEC AND IRC