Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/12/2005 | FRAMING | Partial Approval | IVRS - Inspection :* USE 4 1/2" LAG BOLTS 3/8 DIAMETER @ 32" O.C TO TIE DOWN CRIPPLE WALL USE H2.5 CLIPS JOIST TO TOP OF CRIPPLE WALL ADD 2X6 TO BUILD UP BEAM, NAIL WITH 16 D SINKER 12" O,C. FARTHERST NORTH BEAM. PROVIDE STRAPS AT ALL POST TO PROVIDE CONTINUOUS LOAD PATH FOR UP LIFT. ADD POST UNDER RIDGE BOARD. |