Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T05BU02175

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2005 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
10/04/2005 POOL/SPA ELECTRIC Not ready for Inspection IVRS - Inspection :*MEET ELECTRICAL CONTRACTOR ON SITE
09/29/2005 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999* #8 BOND CONDUCTOR TO BE SOLID 680.26
ONLY ONE CONDUCTOR UNDER LUG NOT DOUBLE BACK
BOND ALL ENCLOSURES 680.26
MAINTAIN WORKING AND DEDICATED CLEARANCES ON ALL DISCONNECTS 110.26
PLEASE LABEL ALL DISCONNECTS
TIGHTEN LOOSE FITTINGS
BOND ALL METAL WITHIN 5' OF EDGE OF WATER HORIZONTALLY 680.26. HANDRAILS, GATES, HOIST, JACKS.
WEATHER PROOF COVERS TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8
WHERE IS EMERGENCY SHUT OFF SWITCH
BOND VERITCALLY 12' METAL PARTS
ALL RECEPTACLES TO BE GFCI PROTECTED.