Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2005 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 10/04/2005 | POOL/SPA ELECTRIC | Not ready for Inspection | IVRS - Inspection :*MEET ELECTRICAL CONTRACTOR ON SITE | |
| 09/29/2005 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* #8 BOND CONDUCTOR TO BE SOLID 680.26 ONLY ONE CONDUCTOR UNDER LUG NOT DOUBLE BACK BOND ALL ENCLOSURES 680.26 MAINTAIN WORKING AND DEDICATED CLEARANCES ON ALL DISCONNECTS 110.26 PLEASE LABEL ALL DISCONNECTS TIGHTEN LOOSE FITTINGS BOND ALL METAL WITHIN 5' OF EDGE OF WATER HORIZONTALLY 680.26. HANDRAILS, GATES, HOIST, JACKS. WEATHER PROOF COVERS TO BE WEATHER PROOF WHETHER OR NOT PLUGGED INTO 406.8 WHERE IS EMERGENCY SHUT OFF SWITCH BOND VERITCALLY 12' METAL PARTS ALL RECEPTACLES TO BE GFCI PROTECTED. |