Permit: T05BU01828

Parcel: 121016460


Addresses:

1951 N WILMOT RD 03


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T05BU01828

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2005 FIRE SPKLR - FINAL Approved
12/01/2005 FIRE SPKLR - FINAL Denied 1. Submit revised plans indicating location of full height interior walls extending to roof deck and revised upright fire sprinkler locations.
2. Replace all painted fire sprinklers.
3. Protect exterior riser from corrosion and freezing.
4. Secure inspectors test piping.
5. Supervise main control valve in open position.
11/21/2005 FIRE SPKLR - FINAL Denied Need electrical power to waterflow alarm bell.