Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2005 | FIRE SPKLR - FINAL | Approved | ||
| 12/01/2005 | FIRE SPKLR - FINAL | Denied | 1. Submit revised plans indicating location of full height interior walls extending to roof deck and revised upright fire sprinkler locations. 2. Replace all painted fire sprinklers. 3. Protect exterior riser from corrosion and freezing. 4. Secure inspectors test piping. 5. Supervise main control valve in open position. |
|
| 11/21/2005 | FIRE SPKLR - FINAL | Denied | Need electrical power to waterflow alarm bell. |