Permit: T05BU01805

Parcel: 141134480

Inspection Status: Denied

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
09/26/2005 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POOL COVERS LEFT ON SITE FOR FINAL INSPECTION WERE NOT USED-DIFFERNET TYPE WERE INSTALLED
09/22/2005 POOL/SPA FINAL/BARRIER Partial Approval IVRS - Inspection :*
2ND WINDOW NEEDS NON REMOVABLE SCREW DET AT 4"
09/21/2005 POOL/SPA FINAL/BARRIER Partial Approval IVRS - Inspection :*
1) POOL COVERS TO BE A.S.M.E. APPROVED
09/20/2005 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED A 2 POLE 20/20 BREAKER FOR POOL PANEL 30/30 INSTALLED #12 CU WIRE
2) BOND WIRE CONNECTION IN WET NICHE FIXTURE NOT PROTECTED
3) NEED G.P.M OF SYS ON PLAN. LEAVE A.S.ME APPROVED COVERS ON SITE
4) PIN WINDOWS SO THAT THEY WON'T OPEN MORE THAN 4" O.C.