Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/27/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/20/2005 ELECTRIC - FINAL Denied REINSPECTION FEE DUE PRIOR TO NEXT ( 3RD) INSPECTION. 1. MOVE GROUNDING ELECTRODE CONNECTION DIRECTLY TO NEUTRAL AS REQUESTED LAST TIME. SEE N.E.C FOR ASSISTANCE. 2) ITEMS ( PREVIOUS # 1,2,3 NOT CORRECTED)
06/16/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR( NEUTRAL BUS) DIRECTLY AS PER NATIONAL ELEC. CODE 2) EQUIP GROUNDING BUS BAR IS NOT ALLOWED PER 110-3 TO BE INSTALLED USING SHEET METAL OR SELF TAPPONG SCREWS ( NOTE : YOU NEED TO BOND NEUTRAL AT PANEL ANYWAY TO ENCLOSURE SO YOU DON'T. 3) INSTALL BOND BUSHING AT 2" OFFSET NIPPLE