Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/20/2005 | ELECTRIC - FINAL | Denied | REINSPECTION FEE DUE PRIOR TO NEXT ( 3RD) INSPECTION. 1. MOVE GROUNDING ELECTRODE CONNECTION DIRECTLY TO NEUTRAL AS REQUESTED LAST TIME. SEE N.E.C FOR ASSISTANCE. 2) ITEMS ( PREVIOUS # 1,2,3 NOT CORRECTED) | |
| 06/16/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUNDED CONDUCTOR( NEUTRAL BUS) DIRECTLY AS PER NATIONAL ELEC. CODE 2) EQUIP GROUNDING BUS BAR IS NOT ALLOWED PER 110-3 TO BE INSTALLED USING SHEET METAL OR SELF TAPPONG SCREWS ( NOTE : YOU NEED TO BOND NEUTRAL AT PANEL ANYWAY TO ENCLOSURE SO YOU DON'T. 3) INSTALL BOND BUSHING AT 2" OFFSET NIPPLE |