Permit: T05BU01287

Parcel: 127080970


Addresses:

5458 E 7TH ST

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
08/19/2005 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
08/18/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) EXPOSE UNDERGROUND ELECTRIC
2) RAISE GATE LATCH TO 54"
3) REDUCE AREA UNDER FENCE TO LESS THAN 4"
08/16/2005 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) TWO BREAKERS IN PANEL ARE DBL LUGGED
2) FENCE ON NORTH SIDE OF POOL NOT BONDED
07/13/2005 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NON-METAL CONDUIT MUST BE 18" DEEP BETWEEN EQUIPMENT AND PANEL
2) NOTE FOR CONTRACTOR-PATIO BOND WIRE MUST GO UP TO DRIP EDGE
3) NOTE FOR OWNER-A DBL GATE CANNOT BE USED AS A POOL BARRIER