Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/19/2005 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 08/18/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) EXPOSE UNDERGROUND ELECTRIC 2) RAISE GATE LATCH TO 54" 3) REDUCE AREA UNDER FENCE TO LESS THAN 4" |
|
| 08/16/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) TWO BREAKERS IN PANEL ARE DBL LUGGED 2) FENCE ON NORTH SIDE OF POOL NOT BONDED |
|
| 07/13/2005 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NON-METAL CONDUIT MUST BE 18" DEEP BETWEEN EQUIPMENT AND PANEL 2) NOTE FOR CONTRACTOR-PATIO BOND WIRE MUST GO UP TO DRIP EDGE 3) NOTE FOR OWNER-A DBL GATE CANNOT BE USED AS A POOL BARRIER |