Permit: T05BU01059

Parcel: 116124850

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Permit Number - T05BU01059

Inspection Description - FIRE - KITCHEN EXH HOOD FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2008 FIRE - KITCHEN EXH HOOD FINAL Approved
01/22/2008 FIRE - KITCHEN EXH HOOD FINAL Denied MAKE-UP AIR NOT SHUTTING DOWN.
10/23/2007 FIRE - KITCHEN EXH HOOD FINAL Denied NEED AS-BUILT. NEED PROPER NOZZLE IN PLENUM. NEED 450-500 TEMP. DETECTOR OVER FRYER. NEED 360 TEMP. DETECTOR OVER RANGE. NEED TO BRACE APPLIANCE PIPING.
06/15/2006 FIRE - KITCHEN EXH HOOD FINAL Cancelled
11/21/2005 FIRE - KITCHEN EXH HOOD FINAL Denied MICRO-SWITCH NOT CONNECTED FOR ELECT. & MAKE-UP AIR SHUT DOWN