Permit: T05BU00522

Parcel: 136327210

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
07/21/2005 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection :*
1) KEEP IN ACTIVE SIDE OF DBL GATE BOLTED SHUT AT CANE BOLT
07/11/2005 POOL/SPA FINAL/BARRIER Not ready for Inspection IVRS - Inspection :*
1) SEE LAST INSPECTION
07/07/2005 POOL/SPA FINAL/BARRIER Not ready for Inspection IVRS - Inspection :*
1) CONNECTION STRANDED CO. WIRE (BOND) IN WET NICHE FIXTURE TO BE ENCAPSULATED WITH POTTING COMPOUND
2) NEED CONCRETE OVER PLASTIC ELECTRIC CONDUIT NOT 18" BELOW GRADE
3) REPLACE ANTI-SIPHON AT HOSE BIB
4) STINGLE VALVES ARE APPROVED BUT MUST BE INSTALLED
5) SERVICE PANEL LABEL FOR CIRCUITS NOT CORRECT, TWO WIRES IN A SINGLE LUG BREAKER, CIRCUIT FOR POOL PANEL BOARD IS NOT ON 2 POLE BREAKER
6) ALL DOORS TO BE SELF CLOSING AND LATCHING WITH THE LATCH AT 54" ABOVE F. FLOOR
7) POOL DRAIN COVER TO BE RATED AT OR ABOVE ? GALLON PER MINUTE OF SYSTEM FLOW RATE