Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2005 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection :* 1) KEEP IN ACTIVE SIDE OF DBL GATE BOLTED SHUT AT CANE BOLT |
|
| 07/11/2005 | POOL/SPA FINAL/BARRIER | Not ready for Inspection | IVRS - Inspection :* 1) SEE LAST INSPECTION |
|
| 07/07/2005 | POOL/SPA FINAL/BARRIER | Not ready for Inspection | IVRS - Inspection :* 1) CONNECTION STRANDED CO. WIRE (BOND) IN WET NICHE FIXTURE TO BE ENCAPSULATED WITH POTTING COMPOUND 2) NEED CONCRETE OVER PLASTIC ELECTRIC CONDUIT NOT 18" BELOW GRADE 3) REPLACE ANTI-SIPHON AT HOSE BIB 4) STINGLE VALVES ARE APPROVED BUT MUST BE INSTALLED 5) SERVICE PANEL LABEL FOR CIRCUITS NOT CORRECT, TWO WIRES IN A SINGLE LUG BREAKER, CIRCUIT FOR POOL PANEL BOARD IS NOT ON 2 POLE BREAKER 6) ALL DOORS TO BE SELF CLOSING AND LATCHING WITH THE LATCH AT 54" ABOVE F. FLOOR 7) POOL DRAIN COVER TO BE RATED AT OR ABOVE ? GALLON PER MINUTE OF SYSTEM FLOW RATE |