Permit: T05BU00481

Parcel: 11616301C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/21/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* TESTED EPO- CHECKED SEALS-CONTRACTOR TAPING WHITE TO RED
03/18/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* ALEX CALLED YOU OFFICE AT 9:15AM, THEY COULD NOT GET A HOLD OF YOU. NEED TO MEET YOU HERE TO OPEN NEW SEALS & VERIFY E?? SWITCH WORK ABILITY. PLS RECALL AND LEAVE ME A # TO CONTACT YOU PRIOR TO INSPECTION.
03/16/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* UNDERGROUND OK TO COVER. CALL FOR FINAL ONCE COVERED AND MEET ME ON SITE OT TEST SYSTEM ?? SHUT OFF SERV.
03/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) PROVIDE ADEQUATE SUPPORT FOR 1/2" RIGID AT TANK BOTH SIDES. 2) VERIFY EMERGENCY DISCONNECTS LPG WIRING OR PROVIDE ITS OWN SAFETY SHUT OF FOR WIRING AS PER NEC 2002.
03/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CALLED CONTRACTOR AS HIS MESSAGE ASKED ME TO DO ( HE NEVER SHOWED UP TO OPEN UP EQUIP)