Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2005 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 04/21/2005 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST HAVE 36" BETWEEN SUCTION COVERS AT BOTTOM OF POOL 2) INSTALL S.V.R.S AT SUCTION LINE AT EQUIPMENT 3) UNCOVER NEW ELECTRIC RUN FROM MAIN PANEL TO POOL EQUIPMENT (NEVER INSPECTED PER PREVIOUS PAPERWORK) 4) CHAIN LINK FENCE MUST CONTINUE SLAT INSTALL BEHIND WOODEN SHED 5) GATES TO BE SELF-CLOSING AND SELF-LATCHING 6) STOPPED INSPECTION |
|
| 03/18/2005 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) ELECTRIC FROM ELECTRIC SERVICE TO POOL EQUIPMENT NOT RUN 2) OK TO GUNITE 3) RECALL AFTER INSTALLING ELECTRIC STATED ABOVE AND BEFORE BACK FILLING PRIOR TO FINAL |