Permit: T04PL02270

Parcel: 131020190


Addresses:

1709 S WOODLAND AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/19/2005 PLUMBING - FINAL Approved IVRS - Inspection :* 15 PSI TEST IS OK LEFT GAS CARD CORRECTIONS HAVE BEEN MADE.
12/29/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/PROVIDE PERMIT FOR NEW FURNACE. 1)PROVIDE MINIMUM 10 PSI TEST AT TIME OF INSPECTION, SHALL HOLD WITH NO PRESSURE DROP FOR 15 MINUTES 2)PROVIDE AGA OR CSA GAS VALVES AT ALL APPLIANCES 3)PROVIDE BONDING OF BUILDING GAS PIPING SYSTEM