Permit: T04PL02260

Parcel: 132102700

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/31/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE
12/28/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)SHALL PROVIDE A AIR PRESSURE TEST ON ENTIRE SYSTEM @ 10 LBS MIN @ TIME OF INSPECTION 2)SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES @ ALL APPLIANCES 3)SHALL PROVIDE AIR COMBUSTION VENTS LOCATED 12" BELOW CEILING AND 12" ABOVE FLOOR. MIN. 10X10 GRILLS 4)SHALL TAPE PRIMER AND WRAP WITH 10 MIL TAPE ALL FITTINGS UNDERGROUND 5)MIN COVER OF PIPE UNDERGROUND IS 12". CHECK THE TRENCH 6)SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT AND @ APPLIANCE COLLAR FOR WATER HTR FLU VENT 7)SHALL SEAL GAS LINE PENETRATION @ REAR OF HOUSE ENTRY 8)SHALL OBTAIN PETITION OF APPEAL FROM OUR OFFICE FOR ALTERNATE METHOD OF T&P DRAIN PRIOR TO INSPECTION