Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/15 PSI AIR TEST FROM METER TO (2) FUTURES AND ROOF TOP UNIT ONLY OK. GAS CARD AT METER SW GAS 889-1888 1)PROVIDE BONDING OF BUILDING GAS PIPING | |
| 12/22/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/10 PSI AIR TEST SHALL HOLD FOR 15 MINUTES |
|
| 12/21/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)PROVIDE PERMIT FOR MEW ROOF TOP UNIT. 2)PROVIDE BONDING OF BUILDING GAS PIPING. 3)USE APPROVED COUPLINGS, WHERE UNIONS ARE NECESSARY LEFT & RIGHT NIPPLES & COUPLINGS SHALL BE USED 4)10 PSI AIR TEST AT TIME OF INSPECTION |