Permit: T04PL02217

Parcel: 137101680


Addresses:

929 W NEBRASKA ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/22/2004 PLUMBING - GAS PRESSURE TEST Approved THE ONLY CORRECTION REMAINING WAS THE USE OF A "T" FITTING IN THE GAS LINE FOR FUTURE USE. SPOKE TO DAVE MANN AND WE BOTH AGREE THAT THIS FITTING IS ACCEPTABLE.
12/22/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/CAN NOT HAVEA FLEX CONNECTOR PENETRATE THE FURNACE HOUSING. THIS MUST BE HARD PIPED THEN CONNECT THE FLEX CONNECTOR 2)SHALL EXTEND FLU VENT 3'0" ABOVE COOLER 3)SHALL REMOVE TEE WITH PLUG @ HOUSE SUPPLY ENTRY 4)BLK PIPE IS NOT APPROVED MATERIAL FOR T&P DRAIN AND CONNOT HAVE THREADS @END OF PIPE TERMINATION 5)RE TEST THE SYSTEM 6)OK TO BACKFILL TRENCH

1)SHALL REMOVE TEE WITH PLUG @ HOUSE SUPPLY ENTRY AS REQUESTED 2)SHALL PAY A REINSPECTION FEE PRIOR TO NEXTA INSPECTION
12/21/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/10 PSI PRESSURE TEST SHALL HOLD FOR MINIMUM OF 15 MINUTES