Permit: T04PL02214

Parcel: 12406030A


Addresses:

907 E 8TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T04PL02214

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2005 PLUMBING - FINAL Approved IVRS - Inspection :*/1)CORRECTIONS MADE OK 2)OK FOR GAS 3)UCC LEFT AT METER SW GAS 889-1888
01/03/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*1) SEE 514.2 94 UPC VENT CONNECTOR REQUIRE 3 SHEET METAL SCREWS, RIVETS OR OTHER APPROVED MEANS-SHEET ROCK SCREWS NOT APPROVED. 2) INSTALL APPROVED REDUCER FROM 4" TO 3" 3) OK TO COVER UNDERGROUND PIPING. 4) SEAL EXTERIOR WALL PENETRATION 313.8 5) SEE 313.8 GAS PIPE REQURES FLASHING PASSING THROUGH ROOF. 6 PLEASE CALL IN ALL REQD INSPECTIONS. PLEASE HAVE AN ADULT PRESENT TO ASSIST THE INSPECTOR.
12/28/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)GAS LINE MAYH NOT RUN UNDER THE BUILDING 2)NEITHER WATER HEATER HAS AN APPROVED VENT NOR DO EITHER ONE HAVE A T&P RELIEF DRAIN, (EVIDENCE OF T&P DRAIN LEAKING ON BOTH) 3)NO BONDING