Inspection History: PLUMBING - FINAL
Permit Number - T04PL02214
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/1)CORRECTIONS MADE OK 2)OK FOR GAS 3)UCC LEFT AT METER SW GAS 889-1888 | |
01/03/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*1) SEE 514.2 94 UPC VENT CONNECTOR REQUIRE 3 SHEET METAL SCREWS, RIVETS OR OTHER APPROVED MEANS-SHEET ROCK SCREWS NOT APPROVED. 2) INSTALL APPROVED REDUCER FROM 4" TO 3" 3) OK TO COVER UNDERGROUND PIPING. 4) SEAL EXTERIOR WALL PENETRATION 313.8 5) SEE 313.8 GAS PIPE REQURES FLASHING PASSING THROUGH ROOF. 6 PLEASE CALL IN ALL REQD INSPECTIONS. PLEASE HAVE AN ADULT PRESENT TO ASSIST THE INSPECTOR. | |
12/28/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/1)GAS LINE MAYH NOT RUN UNDER THE BUILDING 2)NEITHER WATER HEATER HAS AN APPROVED VENT NOR DO EITHER ONE HAVE A T&P RELIEF DRAIN, (EVIDENCE OF T&P DRAIN LEAKING ON BOTH) 3)NO BONDING |