Permit: T04PL02200

Parcel: 136153810

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T04PL02200

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*/15 PSI PRESSURE TEST TO POOL HEATER AND (2) ROOF TOP UNITS ONLY OK. CORRECTIONS MADE. GAS CARD AT METER SW GAS 889-1888
12/21/2004 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)REPLACE THREAD PROTECTOR WITH APPROVED COUPLING AT NORTH ROOF TOP UNIT. 2)SUPPORT PIPING AT CORRECT INTERVALS AT ROOF TOP UNITS 3)SUPPORT GAV PIPING AT POOL HEATER PROPERLY 4)POOL HEATER TEMPERATURE & PRESSURE RELIEF TO BE TERMINATED AT 6" - 24" AT DOWNWARD ANGLE TO PREVENT SLADING 5)BOTH PIPING SYSTEMS TO HOLD MINIMUM 10 PSI FOR 15 MINUTES 6)PROVIDE BONDING OF BUILDING GAS PIPING