Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/1)ALL CORRECTIONS HAVE BEEN MADE | |
| 12/22/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)GAS PRESSURE TEST IS OK. 2)GAS SHUT OFF VALVES OK 3)OK TO BACKFILL TRENCH 4)CAN NOT HAVE A FLEX CONNECTOR PENETRATE THE WATER HTR ENCLOSURE. THIS SHALL BE HARD PIPED INTO ENCLOSURE THEN CONNECT VALVE & FLEX LINE5)WATER HTR FLU VENT APPEARS TO HAVE NEGATIVE PITCH 1/4" PER FT MIN PITCH 6)SHALL SEAL ALL GAS LINE PENETRATIONS THRU WALLS EXTERIOR ONLY |