Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HTR FLU VENT IS OK. T & P VALVE AND DRAIN IS OK 4) FURNACE FLU VENT IS OK |
|
| 12/14/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : 1) SHALL PROVIDE ONE 10 x 10 LOUVER GRILL LOCATED 12" BELOW CEILING 2) SHALL CUT OFF TREADS @ END OF T & P DRAIN AND REPLACE T & P VALVE THAT IS NOT WORKING 3) GAS LINE FOR KITCHEN SINK SHALL BE A MIN OF 6" ABOVE FLOOR AND STRAP DOWN WITH APPROVED STRAPS 4) OK TO BACKFILL TRENCH |