Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/15/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/CORRECTION MADE 889-1888 |
| 12/14/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*1) WATER HEATER TEMPERATURE & PRESSURE RELIF TO TERMINATE AT 90 DEGREE DOWN 6"-24" FROM FINISH GRADE. 2) PROVIDE BONDING OF BUILDING GAS PIPING. 3) PROVIDE FITTING TO MAKE CHANGE OF DIRECTIONON ROOF TOP PIPING |