Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/03/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) 29 PSI AIR TEST FROM MOTOR OVERHEAD TO STOVE, WALL HEATER, WATER HEATER AND DRYER OK 2) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES ON WATER HEATER VENT THRU ROOF. USE NO TAR ON DBL WALL VENT 3) SECURE WATER HEATER VENT USING APPROVED HANGERS AT EACH END |
|
| 12/01/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/9:30 AM PLEASE HAVE SOMEONE PRESENT ON DAY OF CALL IN FOR RE-INSPECTION |