Permit: T04PL02086

Parcel: 122040210


Addresses:

1822 N BELL AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/21/2004 PLUMBING - FINAL Approved IVRS - Inspection :*
11/30/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)PROVIDE ROOF FLASHING FOR VENT FROM WATER HEATER 2)PROVIDE DOUBLE WALL VENT TO POINT OF TERMINATION 3)ROOF TOP PIPING TO BE SUPPORTED & SECURED AT CORRECT INTERVALS 4)PROVIDE BONDING OF BUILDING GAS PIPING 5)WATER HEATER TO SIT ON CONCRETE 6)WATER HEATER T&P DRAIN TO BE SOLDERED?. 7)PVC SCH 40 PIPING CANNOT BE USED FOR WATER SUPPLY INSIDE OF BUILDING OR STRUCTURE, AND CANNOT BE IMBEDDED IN CONCRETE 8)WALL HEATER VENT TO BE 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE. THIS MAY NOT BE A COMPLETE LIST.