Permit: T04PL02065

Parcel: 110102530


Addresses:

5051 E GLENN ST

Inspection Status: Partial Approval

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
05/05/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE ON REVISED PLAN. AS PER LAST REQUEST. ALL VERIFICATION OF GRADE HAS BEEN SENT TO RECORDS. WILL NEED CERTIFICATE OF COMPLETION FROM PIMA COUNTY BEFORE FINAL IS GIVEN
05/02/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* PLEASE NOTE: WILL NEED A REVISION ON VENT AT LIFT STATION ON INSTALL VENT AS PER PLAN. WILL NEED CERTIFICATE OF COMPLETION FROM P.C D.E.Q. AT TIME OF FINAL. VERIFICATION OF GRADE ON JOB AT TIME OF FINAL. PLEASE NOTE: YOUR REVISED PLAN WILL NEED TO GO THRU PLAN CHECK FOR APPROVAL.
04/29/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
04/06/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) FROM M-H #3 TO LIFT STATION-W/Z=HCS TEST OK
SEE NOT 3/15/05 AND 3/16/05
03/17/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* MAN? TEST FROM M-H #1 TO MH #2 TO MH #3 & TO PRIVATE LIFT STATION TEST OK NEED PRESSURE TEST FROM M-H #3 TO LIFT STATION.
03/16/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :* PLEASE SEE DETAIL ON LIFT STATION FOR SIZE OF VENT PLAN CALLS FOR 4"VENT 3" HAS BEEN INSTALLED & REDUCED TO 2" WITH FILTER ?. PLEASE PROVIDE AN APPROVED REVISED PLAN OR INSTALL AS PER APPROVED PLAN.
03/15/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* PLEASE NOTE WILL NEED VERIFICATION OF GRADE ON SITE SEWER ALSO CERTIFICATE OF COMPLETION FROM PIMA COUNTY ENVIRONMENTAL QUALITY AT TIME OF FINAL. FROM M-H # 3 TO M-H #2. TEST OK. 3" PRESSURE SEWER FROM LIFT STATION TO DISCHARGE MANHOLE # 3 EXISTING. TEST OK
03/14/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :*
03/11/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* VACUUM TEST M-H # 3 TEST OK 28?? VACUUM TEST M-H #2-TEST OK 20?. VACUUM TEST M-H #1 TEST OK 25??
03/08/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :* INSP ON SITE SEWER AS PER LETTER OF AGREEMENT JAN 3/05 AGREED TO BY DAVE MANN- BUILDING OFFICIAL & GREGOR& GRENIER ENGINEERING. MARCH 8/05 LOW PRESSURE AIR TEST FROM M-H #1 TO M-H #3 8" SDR-35 NOT READY WILL REQUIRE ?? OF GRADE-VACUUM TEST ON MANHOLES-MAIN??