Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/22/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :* |
| 11/18/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/1)REPLACE THREAD PROTECTOR WITH APPROVED COUPLING 2)PRIME & TAPE ALL TOOL MARKS & FITTING BELOW GROUND LEVEL. 3)UNION SHALL BE PRECIEDED BY APPROVED VALVE OR PROVIDE LEFT-RIGHT NIPPLE & COUPLING AT BUILDING ENTRY AREA 4)ALL APPLIANCES TO HAVE AGA OR CSA APPROVED GAS VALVES 5)WATER HEATER TEMPERATURE & PRESSURE RELIEF TO RIDGID PIPE GRAVITY DRAIN TO DAYLIGHT 6)PROVIDE PROPER BONDING OF BUILDING GAS PIPING 7)VENT FROM WATER HEATER WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE TOP OF COOLER INTAKE. 8)RETEST MINIMUM 10 PSI WITH NO PRESSURE LOSS FOR 15 MINUTES |