Permit: T04PL02046

Parcel: 136203430


Addresses:

3731 S LE BEAUX PL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/22/2004 PLUMBING - FINAL Approved IVRS - Inspection :*
11/18/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/1)REPLACE THREAD PROTECTOR WITH APPROVED COUPLING 2)PRIME & TAPE ALL TOOL MARKS & FITTING BELOW GROUND LEVEL. 3)UNION SHALL BE PRECIEDED BY APPROVED VALVE OR PROVIDE LEFT-RIGHT NIPPLE & COUPLING AT BUILDING ENTRY AREA 4)ALL APPLIANCES TO HAVE AGA OR CSA APPROVED GAS VALVES 5)WATER HEATER TEMPERATURE & PRESSURE RELIEF TO RIDGID PIPE GRAVITY DRAIN TO DAYLIGHT 6)PROVIDE PROPER BONDING OF BUILDING GAS PIPING 7)VENT FROM WATER HEATER WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE TOP OF COOLER INTAKE. 8)RETEST MINIMUM 10 PSI WITH NO PRESSURE LOSS FOR 15 MINUTES