Permit: T04PL02035

Parcel: 10612129A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T04PL02035

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2004 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/17/2004 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*/1)HAVE MINIMUM 10 PSI AIR TEST ON ENTIRE SYSTEM AT TIME OF NSPECTION 2)PROVIDE AGA OR CSA GAS VALVES AT ALL APPLIANCES 3)SUPPORT ALL PIPING AT CORRECT INTERVALS WITH APPROVED METHODS. 4)RIDGID PIPE THRU CABINET PARTITIONS 5)REMOVE FLEX FROM IN LINE PIPING AND RIDGID PIPE GAS SYSTEM