Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/17/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/CORRECTION MADE. 15 SPI AIR TEST FROM NEW METER LOCATION TO (3) WATER HEATERS, (2) FURNACES AND STOVE COOK TOP OK SW GAS 889-1888 GAS CARD AT METER |
| 11/16/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/1)WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLES & COUPLINGS SHALL BE USED 2)UNDERGROUND PIPING TO BE PRUNED & TAPED AT FITTINGS & ALL TOOL MARKS AND BE MINIMUM 12" BELOW FINISH GRADE. 3)ABOVE GRADE PIPING TO BE 6" MINIMUM ABOVE FINISH GRADE 4)SHALL HAVE ACCESS TO ENTIRE GAS SYSTEM |