Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/18/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PROVIDE A MIN 10LB TEST ON GAS SYSTEM. TAPE IS LOOSE ON UNDERGROUND JOINTS. BE SURE ENTIRE JOINT IS PRIMERED & TAPED & ALSO ALL WRENCH MARKS & SCRAPES. 2)GAS PIPE CANNOT LAY ON THE FLOOR IN LAUNDRY ROOM. MUST BE MIN. 6" ABOVE & SECURED 3)REPLACE DRYER VENT WITH A CAP & BACKDRAFT DAMPER. 4)PRESSURE GAUGE IS DAMAGED. REPLACE GAUGE. DO NOT EXCEED 30 PSI GAUGE |