Permit: T04PL01872

Parcel: 128020880


Addresses:

6242 E TIMROD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/26/2004 PLUMBING - FINAL Approved IVRS - Inspection :*
10/18/2004 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)PROVIDE A MIN 10LB TEST ON GAS SYSTEM. TAPE IS LOOSE ON UNDERGROUND JOINTS. BE SURE ENTIRE JOINT IS PRIMERED & TAPED & ALSO ALL WRENCH MARKS & SCRAPES. 2)GAS PIPE CANNOT LAY ON THE FLOOR IN LAUNDRY ROOM. MUST BE MIN. 6" ABOVE & SECURED 3)REPLACE DRYER VENT WITH A CAP & BACKDRAFT DAMPER. 4)PRESSURE GAUGE IS DAMAGED. REPLACE GAUGE. DO NOT EXCEED 30 PSI GAUGE